Cordon control: Cylinders and pressurised gas

Control measure knowledge

Personnel may encounter cylinders and pressurised gases during incidents where their involvement is not expected. It is vital that they recognise them quickly when firefighting.

Initial cordon/hazard areas

Responders inside the initial cordon should use shielding and don appropriate personal protective equipment (PPE). For example, responders likely to be affected by a fireball or blast should wear breathing apparatus (BA) and full structural firefighting kit. See Personal Protective Equipment: Hazardous materials for more information. 

The following key questions will assist incident commanders in assessing the immediate risk:

  • Are there cylinders at the incident?
  • Are the cylinders involved in fire? (i.e. is there direct flame contact, fire damage or radiated heat damage from the fire)
  • Are any cylinders leaking, venting, bulging or steaming?
  • What gases are involved?
  • How many cylinders are there and what size are they?
  • What is the temperature of the cylinder(s)?
  • Is any shielding provided by any buildings or structures?
  • What type of adjacent structures are there and what is their extent?
  • What is the local topography (e.g. protection provided by slopes and gradients of ground levels etc?)
  • What would be the effect of:
    • A potential blast pressure wave
    • A fireball (can travel up to 25 metres)
    • Projectiles (a cylinder may be thrown up to 150 metres* and cylinder fragments and other projectiles such as the valve assembly may be thrown up to 200 metres*)
    • Flying glass and other structural material?
  • What structural damage could be caused to buildings in the vicinity?
  • Is there a need for an exclusion zone within the hazard area?
  • Are other hazards inside or close to the initial cordon?
  • How close are surrounding buildings and infrastructure?
  • Are any buildings or infrastructure occupied or in use?

As an illustration, a 40kg 1000L cylinder travel up to 150m and create a fireball that can travel up to 25m, assuming it is not within a structure or building that would provide substantial shielding.

If cylinders, including acetylene, have not been heated then they do not represent a hazard and should be handed over to the site operator. In a developing fire situation, consider carefully moving them if there is a risk that the fire will spread and involve them.

Where members of the public are within the identified hazard area, the incident commander may wish to consider evacuation. Where this is not possible or appropriate, attempts should be made to warn of the risks and give advice to stay away from windows and doors and stay in rooms furthest away from the risk.

For further information regarding evacuation see National Operational Guidance: Operations Evacuations and shelter.

Strategic actions

Fire and rescue services should:
  • Provide procedures and support arrangements for the hazards that may be encountered and actions to take when gases under pressure are identified as being involved in fire

  • Be proactive in collecting information on the location and type of hazardous gases within the area of their authority

  • Make significant information regarding explosive gases under pressure available to mobilising controls and operational staff

  • Have liaison and contact arrangements in place to deal with emergencies involving gas cylinders with the gas cylinder supply companies. (details available via the British Compressed Gas Association (BCGA))

  • Ensure that all personnel are able to identify compressed gas cylinders from their size, shape, colour and identifying markings

  • Make information regarding appropriate cordon sizes for incidents involving compressed gas cylinders available to all personnel

Tactical actions

Incident commanders should:
  • Establish exclusion zones, inner and outer cordons based on level of risk from cylinders and pressurised gases

  • Position response vehicles outside any potential fireball and blast zone when cylinders are involved in fire

  • Gather information from all relevant sources to identify cylinders involved in fire, including

    • Contents of cylinders
    • Number and size
    • Condition (including temperature)
    • Possible impact
  • Assess any immediate personnel and public life risks and gather information to establish an initial cordon

  • Consider evacuating the potential blast zone and give evacuation or shelter-in-place guidance to those within range of projectiles

  • Ensure responders inside the initial cordon make use of substantial shielding and appropriate personal protective equipment (PPE)

  • Ensure that firefighters use all available substantial shielding/cover within the range of cylinders

  • Consider carefully moving any cylinders that have not been heated to a safe location when in a developing fire situation

  • Consider a minimum initial responder observation distance of 90 metres for LPG tanks/containers over 100 litres or 40kg mass